Our china 220kv Step-down transformers in substations and step-up transformers in power stations are essential components in those facilities. These transformers cover the electric power for many of electricity consumers, so highly reliable transformers are required.
We are making transformers to provide the highest efficiency within the limits where economy is not lost. Because of well arranged core construction, no-load loss is reduced.
In relation, to the load loss occupying the majority of total loss, as a result of employing a transposed conductor, achieving non-magnetization of metal adjacent to the winding, and providing a magnetic shielding of tank inner wall, stray-load loss has been reduced significantly whereby transformers with high efficiency and little loss have been created.
High and Low voltage bushings
Off-circuit tap changer
Lifting lugs
Earthing terminals
Buchholz relay
Dehydrating breather
Pressure relief device
Dial type thermometer
Oil level gauge / Oil level indicator
Filling lug
Skid base
Drain valve
Rating plate
Specification
Main Technical Parameters for oil-immersed power transformer | ||||||||
Rated Power(kva) | High Voltage(kv) | H.V.Tap range | Low Voltage(kv) | Connection symbol | Short Circuit Impendence | No-load loss(kw) | On-load loss(kw) | No-load current(%) |
6300 |
63 66 69 110 132 138 220 |
±8x 1.25% |
6.3 6.6 10.5 11 33 69 |
YNd11 YNyn0 others |
10-14 | 9.4 | 34 | 0.63 |
8000 | 11.2 | 40.4 | 0.63 | |||||
10000 | 13.1 | 47.6 | 0.75 | |||||
12500 | 15.4 | 56.5 | 0.53 | |||||
16000 | 18.5 | 69.5 | 0.49 | |||||
20000 | 21.8 | 84.2 | 0.49 | |||||
25000 | 25.6 | 99.5 | 0.4 | |||||
31500 | 30.4 | 120 | 0.4 | |||||
40000 | 36.2 | 140.3 | 0.39 | |||||
50000 | 42.6 | 174.3 | 0.39 | |||||
63000 | 52 | 210 | 0.39 | |||||
75000 | 60 | 238 | 0.49 | |||||
90000 | 69 | 274 | 0.49 | |||||
120000 | 85 | 328 | 0.46 | |||||
150000 | 101 | 385 | 0.42 | |||||
160000 | 105 | 404 | 0.42 | |||||
180000 | 115 | 436 | 0.42 | |||||
240000 | 144 | 539 | 0.4 |